Allen-Bradley Electrical Items in Pakistan

In a motor control panel, the contactor, the overload relay and the 24 V power supply are three separate parts that must match each other. Allen-Bradley catalog numbers encode the current rating, coil voltage and auxiliary contacts in a few characters, so one wrong letter can mean a coil that doesn’t match your control supply.

HAT INDUSTRIES helps businesses across Pakistan identify and source Allen-Bradley panel components. We are not an authorized Allen-Bradley distributor or stockist. Every order is sourced on request through established, authorized channels, and we confirm the full catalog number with you before ordering.

Bulletin 100-C IEC Contactors

Allen-Bradley’s 100-C contactors are compact, motor-load-rated devices for starting and stopping motors, pumps and conveyors.

Catalog NumberRatingPolesCoilAux Contact
100-C09D109 A (AC-3)3110 V 50 Hz / 120 V 60 Hz AC1 N.O.
100-C23D1023 A3110 V 50 Hz / 120 V 60 Hz AC1 N.O.

How to read the catalog number: In 100-C09D10, “C09” is the 9 A frame, “D” is the coil code (110/120 V AC), and “10” means one normally open auxiliary contact is fitted. The 100-C09 is rated 2 HP at 230 V and 5 HP at 460 V (three phase).

Check the coil before ordering. Pakistan’s single-phase control supply is typically 220–240 V. A 110/120 V coil fitted to a 230 V control circuit will fail, so confirm the coil voltage and ask for the matching coil code. Other coil voltages (such as 24 V DC) use a different letter in the catalog number.

Bulletin 193-EC E3 Plus Electronic Overload Relays

The 193-EC E3 Plus is an electronic overload relay with an internal ground fault sensor. It is sized by adjustable current range.

Catalog NumberFull Load Current Range
193-EC2PB0.4–2 A
193-EC2AB1–5 A
193-EC2BB3–15 A
193-EC2CB5–25 A

In 193-EC2BB, “193” is the E3 overload family, “EC2” is the E3 Plus with internal ground fault sensor, and “B” is the 3–15 A adjustment range. The “B” here is also the contactor size code, so the 193-EC2BB pairs with 100-C09 to 100-C23 contactors. Pick the range that brackets your motor’s full-load current, not just its kW.

Bulletin 1606 Switched Mode Power Supplies

These supplies provide the 24 V DC rail for PLCs, relays and sensors.

Catalog NumberAC InputOutputRating
1606-XLE80EStandard24–28 V DC80 W / 3.3 A
1606-XLE120EN90–132 V AC24–28 V DC120 W / 5 A
1606-XLE120EE180–264 V AC24–28 V DC120 W / 5 A
1606-XLE240E100–120 / 200–240 V AC24–28 V DC240 W / 10 A
1606-XLE480EP100–240 V AC24–28 V DC480 W / 20 A

For a 220–240 V single-phase supply, don’t order the -EN version (90–132 V only). Choose the -EE (180–264 V) or a wide-range model such as the XLE240E or XLE480EP. The last letters of the catalog number also matter. For example, the 1606-XLE480EP-D is the DC-input version and must not be confused with the standard AC unit.

Matching the Three Parts

StepCheck
1. MotorFull-load current (A) and voltage
2. ContactorFrame (C09, C23) and coil voltage
3. Overload relayCurrent range covering the motor’s full-load current
4. Power supplyTotal 24 V load plus margin, and AC input range

Frequently Asked Questions

What does the “10” at the end of 100-C09D10 mean?
It indicates one normally open auxiliary contact is fitted.

Can I use a 193-EC2BB with any contactor?
It is intended for the 100-C09 to 100-C23 contactor sizes. Larger contactors need a different overload relay.

How do I choose a 1606 power supply size?
Add up the current drawn on the 24 V rail (PLC, I/O, relays, sensors) and choose a supply with spare capacity.

Do you keep these in stock?
No. We source on demand and confirm availability, pricing, and lead time before you commit.